Specification clause · NCC 2025 Volume One

S20C5 Combined smoke alarm and smoke detection system

Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 5

Open S20C5 on NCC Online ↗

(1) A Class 2 or 3 building or Class 4 part of a building provided with a combination of a smoke alarm system and smoke detection system in accordance with S20C2 must—

be provided with a smoke alarm system complying with S20C3 within sole-occupancy units; and

subject to (2), be provided with a smoke detection system complying with S20C4 in areas not within sole-occupancy units.

(2) In a Class 2 or 3 building or Class 4 part of a building protected with a sprinkler system complying with Specification 17 (other than a FPAA101D or FPAA101H system), smoke detectors are not required in public corridors and other internal public spaces.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S20C5.