S20C6 Smoke detection for smoke control systems
Specification 20 Smoke detection and alarm systems · NCC 2019: Spec E2.2a: 6
(1) Smoke detectors required to activate air pressurisation systems for fire-isolated exits and zone pressurisation systems must—
be installed in accordance with Section 7 of AS 1670.1; and
have additional smoke detectors installed adjacent to each bank of lift landing doors set back horizontally from the door openings by a distance of not more than 3 m.
(2) Smoke detectors required to activate—
automatic shutdown of air-handling systems in accordance with E2D16, E2D17 or E2D19; or
a smoke exhaust system in accordance with Specification 21,
must comply with the requirements of (3).
(3) Smoke detectors referred to in (2) must—
be spaced—
not more than 20 m apart and not more than 10 m from any wall, bulkhead or smoke curtain; and
in enclosed malls and walkways in a Class 6 building not more than 15 m apart and not more than 7.5 m from any wall, bulkhead or curtain; and
have a sensitivity—
in accordance with Section 7 of AS 1670.1 in areas other than a multi-storey walkway and mall in a Class 6 building; and
not exceeding 0.5% smoke obscuration per metre with compensation for external airborne contamination as necessary, in a multi-storey walkway and mall in a Class 6 building.
(4) Smoke detectors provided to activate a smoke control system must—
either—
form part of a building fire or smoke detection system complying with AS 1670.1; or
be a separate dedicated system incorporating control and indicating equipment complying with AS 1670.1; and
activate a building occupant warning system complying with S20C7, except that smoke detectors provided solely to initiate automatic shutdown of air-handling systems in accordance with (2)(a) need not activate a building occupant warning system.
Changed since NCC 2022. See NCC 2022 Volume One S20C6, or show what changed.
(1) Smoke detectors required to activate air pressurisation systems for fire-isolated exits and zone pressurisation systems must — be installed in accordance with Section 7 of AS 1670.1; and have additional smoke detectors installed adjacent to … or curtain; and have a sensitivity — in accordance with Section 7 of AS 1670.1 in areas other than a multi-storey walkway and … with (2)(a) need not activate a building occupant warning system.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Clauses referred to
- E2D16 Class 9b – assembly buildings: nightclubs, discotheques and the like
- E2D17 Class 9b – assembly buildings: exhibition halls
- E2D19 Class 9b – assembly buildings: theatres and public halls (not listed in E2D18) including lecture theatres and cinema/auditorium complexes
- S20C7 Building occupant warning system