Specification clause · NCC 2025 Volume One

S23C3 General requirements

Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 2(a)

Open S23C3 on NCC Online ↗

(1) The installation of a residential local fire alarm system must consist of a system of smoke alarms powered either—

directly from the low voltage supply mains; or

from an extra-low voltage power source originating at a local fire indicator panel with a battery back-up facility.

(2) A smoke detector complying with AS 1670.1 Clause 2.1.2(a)(ii), (xi) or (xv) may be substituted for a smoke alarm, provided an audible alarm device is associated with each detector.

(3) The sound pressure level provided by a warning device must be equivalent to that required in Clause 3.22 of AS 1670.1, except that the sound pressure level need not be measured inside a sole-occupancy unit, provided that a level of not less than 85 dB(A) is attained at the access door to the unit.

(4) The alarm system must be wired for low voltage or extra-low voltage wiring.

(5) The system must be designed so—

an audible alarm is given in the area in which the smoke alarm activates; and

visible and audible indication of an alarm is provided at the local fire indicator panel; and

an audible alarm is given in any area (including sleeping quarters and staff outbuildings) set aside for staff use.

(6) The maximum number of smoke alarms on any one alarm zone must—

be determined by the maximum current output rating of the system source; and

not exceed 10.

(7) Each alarm zone must be located around a single central access passageway, corridor or similar thoroughfare, to enable staff to readily identify the source of the alarm.

(8) Where the smoke alarm is functionally dependent on an external power source—

an audible fault signal must sound at the local fire indicator panel if that power source fails; and

the local fire indicator panel must be permanently connected to a reliable 240 V separate low voltage final sub-circuit; and

source power must be protected by a separate circuit breaker, or fuse, supplied from the live side of the main switch.

(9) The smoke alarm system is not required to be connected to a fire alarm monitoring system (refer to S18C3(2)(c)).

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S23C3.