NCC 2025 Volume One
Specification 23 Residential fire safety systems
9 clauses · Open on NCC Online ↗
- S23C1 ScopeThis Specification describes the requirements for residential fire safety systems referenced in Specification 18.
- S23C2 ApplicationClauses S23C3 to S23C7 — apply to Class 3 residential care buildings; and cover installation requirements for local fire indicator panels (or alarm…
- S23C3 General requirementsThe installation of a residential local fire alarm system must consist of a system of smoke alarms powered either— directly from the low voltage…
- S23C4 Local fire indicator panelThe local fire indicator panel must be located in a central area, such as a reception area, so that it is readily accessible by staff at all times.…
- S23C5 Smoke alarmsExtra-low voltage smoke alarms must be compatible with the local fire indicator panel. (2) Low voltage smoke alarms must be configured to send an…
- S23C6 Signal isolation interface unitsSignal isolation interface units must isolate any low voltage connected to the smoke alarms from the local fire indicator panel. (2) Signal…
- S23C7 WiringSmoke alarms and associated equipment must be fixed wired for low voltage or extra-low voltage wiring systems, as applicable. (2) All extra-low…
- S23C8 Connection to monitoring serviceConnection of a residential sprinkler system to a fire station or other approved monitoring service must be via a sprinkler alarm switch, connected…
- S23C9 Indication at the fire indicator panelThe fire signal from the alarm signalling equipment must be mimicked by an audible and visible signal at the fire indicator panel.