S23C8 Connection to monitoring service
Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 3(a)
(1) Connection of a residential sprinkler system to a fire station or other approved monitoring service must be via a sprinkler alarm switch, connected to alarm signalling equipment.
(2) The connection from the alarm signalling equipment must be in accordance with AS 1670.3.
(3) The alarm signalling equipment must be installed—
in a secure, accessible position; and
in a weatherproof housing, if located externally; and
not more than 500 mm from the system flow switch.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S23C8.