Specification clause · NCC 2025 Volume One
S24C3 Lift car emergency lighting
Specification 24 Lift installations · NCC 2019: Spec E3.1: 3
A lift car must have an emergency lighting system designed—
to come on automatically upon failure of the normal lighting supply; and
to provide at least 20 lux of lighting for 2 hours on the alarm initiation button.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S24C3.