Specification clause · NCC 2025 Volume One

S26C6 Other areas

Specification 26 Waterproofing and water-resistance requirements for building elements in wet areas · NCC 2019: Table F1.7

Open S26C6 on NCC Online ↗

(1) For walls adjoining other types of vessels (e.g. sink, basin or laundry tub), the following applies:

Walls must be water resistant to a height of not less than 150 mm above the vessel, for the extent of the vessel, where the vessel is within 75 mm of a wall.

Waterproof wall junctions where a vessel is fixed to a wall.

Waterproof tap and spout penetrations where they occur in surfaces required to be waterproof or water resistant.

(2) For laundries and WCs, other than WCs as described in (3), the following applies:

Water resistant floor of the room.

Water resistant wall/floor junctions.

Waterproof penetrations where they occur in surfaces required to be waterproof.

(3) For WCs with a handheld bidet spray installation, the following applies:

Waterproof floor of the room.

Walls must be—

waterproof within a 1500 mm radius from the wall connection of the handheld bidet spray device to a height of not less than 150 mm above the floor substrate; and

water resistant within a 1500 mm radius from the wall connection of the handheld bidet spray device to a height of not less than 1200 mm above the finished floor level of the WC.

Waterproof wall junctions within the WC area within 1500 mm radius from the wall connection of the handheld bidet spray device.

Waterproof wall/floor junctions within the WC area within 1500 mm radius from the wall connection of the handheld bidet spray device.

Waterproof penetrations in WC area.

(4) For bathrooms and laundries required to be provided with a floor waste by F2D4, the following applies:

Waterproof floor of the room.

Waterproof wall/floor junctions.

Waterproof penetrations where they occur through the floor.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S26C6.