Specification clause · NCC 2025 Volume One

S27C9 Door and door controls

Specification 27 Accessible adult change facilities · NCC 2019: Spec F2.9: 9

Open S27C9 on NCC Online ↗

The entrance door and associated door controls must be automated and must comply with the following:

The threshold must incorporate a smooth transition without a step or lip.

The minimum clear opening width must be—

1100 mm in locations where beach wheelchairs are likely to be used; or

950 mm in all other locations.

The doorway must achieve a luminance contrast of at least 30% between—

door leaf and door jamb; or

door leaf and adjacent wall; or

architraves (where used) and adjacent wall; or

door leaf and architrave (where used); or

door jamb and adjacent wall.

The operation of the door must be calibrated such that—

it has a gentle opening and closing movement; and

there is sufficient dwell time for a user to safely travel through the doorway.

The door must be fitted with a fail-safe opening mechanism that opens the door if an obstruction is detected during its closing movement.

Door controls must be located internally and externally—

between 900 mm and 1200 mm above finished floor level; and

not less than 500 mm from any internal corner.

Door control buttons must—

have a minimum diameter of 25 mm; and

be proud of the surrounding surface; and

activate the door operation before the button becomes level with the surrounding surface; and

be of a contrasting colour to the surrounding plate.

The surrounding plates of both internal and external door controls must include the words “Push to Open”.

The following indicator lights must be provided:

“Occupied” and “Vacant” on the external plate.

“Locked” and “Unlocked” on the internal plate.

Braille and tactile signage complying with Specification 15 must identify the door controls.