NCC 2025 Volume One
Specification 27 Accessible adult change facilities
11 clauses · Open on NCC Online ↗
- S27C1 ScopeThis Specification contains the requirements for accessible adult change facilities.
- S27C2 General requirementsEach accessible adult change facility must— be constructed so that all required equipment and fixtures are contained within the same room; and if it…
- S27C3 HoistThe hoist must— provide a constant charge in-line room coverage hoist system (also known as an “XY” system or gantry) including 2 parallel fixed…
- S27C4 Toilet pan, seat, backrest and grabrailsThe toilet pan must be of the centrally located ("peninsula-type") design. (2) The toilet pan must be installed so that— the front edge of the pan…
- S27C5 Washbasin and tapThe washbasin must be installed so that the rim of the basin is between 800 mm and 830 mm above finished floor level. (2) Exposed heated water…
- S27C6 Fixtures and fittingsA vertical mirror must be provided at the washbasin, with a reflective surface that— is not less than 600 mm wide; and has its bottom edge not more…
- S27C7 Change tableThe change table must be— permanently installed, with one of the long edges up against a wall and with a retractable safety rail on the opposite…
- S27C8 Changing railsChanging rails must be installed as two horizontal and parallel rails fixed to a wall, not less than 800 mm long, each with a diameter between 30 mm…
- S27C9 Door and door controlsThe entrance door and associated door controls must be automated and must comply with the following: The threshold must incorporate a smooth…
- S27C10 SignageExternal signage must incorporate— the symbol shown in Figure S27C10; and the words “Accessible Adult Change Facility”. (2) The symbol required by…
- S27C11 Operating instructionsSignage provided within the facility must include the following information for the hoist and change table: Operating instructions. Safe working…