Specification clause · NCC 2025 Volume One
S28C2 Discontinuous construction
Specification 28 Sound insulation for building elements · NCC 2019: NT Spec F5.2: 2, Spec F5.2: 1(b)
Varied in NT. Check the variation for your state.
Wall systems listed in S28C4 to S28C7 having a minimum 20 mm cavity between 2 separate leaves are deemed to be discontinuous construction if—
for masonry, where wall ties are required to connect leaves, the ties are of the resilient type; and
for other than masonry, there is no mechanical linkage between leaves except at the periphery.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S28C2.
State and territory variations all clauses side by side →
Clauses referred to
- S28C4 Acceptable forms of construction for walls — masonry
- S28C7 Acceptable forms of construction for walls — timber and steel framing