Specification 28 Sound insulation for building elements · NCC 2019: NT Spec F5.2: Table 2, Spec F5.2: 2

Open S28C3 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) The forms of wall construction described in S28C4 to S28C7 and floor construction described in S28C8 to S28C10, are considered to have the Rw, Rw + Ctr and Ln,w stated in those clauses.

(2) The forms of construction referred to in (1) must be installed as follows:

Masonry units must be laid with all joints filled solid, including those between the masonry and any adjoining construction.

Joints between concrete slabs or panels and any adjoining construction must be filled solid.

For sheeting materials—

if one layer is required on both sides of a wall, it must be fastened to the studs with joints staggered on opposite sides; and

if two layers are required, the second layer must be fastened over the first layer so that the joints do not coincide with those of the first layer; and

joints between sheets or between sheets and any adjoining construction must be taped and filled solid.

Timber or steel-framed construction — perimeter framing members must be securely fixed to the adjoining structure and—

bedded in resilient compound; or

the joints must be caulked so that there are no voids between the framing members and the adjoining structure.

Services must not be chased into concrete or masonry elements.

A door or panel required to have a certain Rw + Ctr that provides access to a duct, pipe or other service must—

not open into any habitable room (other than a kitchen); and

be firmly fixed so as to overlap the frame or rebate of the frame by not less than 10 mm, be fitted with a sealing gasket along all edges and be constructed of—

wood, particleboard or blockboard not less than 33 mm thick; or

compressed fibre-reinforced cement sheeting not less than 9 mm thick; or

other suitable material with a mass per unit area not less than 24.4 kg/m2.

A water supply pipe must—

only be installed in the cavity of discontinuous construction; and

in the case of a pipe that serves only one sole-occupancy unit, not be fixed to the wall leaf on the side adjoining any other sole-occupancy unit and have a clearance not less than 10 mm to the other wall leaf.

Electrical outlets must be offset from each other—

in masonry walling, not less than 100 mm; and

in timber or steel-framed walling, not less than 300 mm.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S28C3.