Specification clause · NCC 2025 Volume One

S28C8 Acceptable forms of construction for floors — concrete

Specification 28 Sound insulation for building elements · NCC 2019: Spec F5.2: Table 3

Open S28C8 on NCC Online ↗

(1) Acceptable forms of construction for concrete floors are set out in (2) to (4).

(2) 150 mm thick concrete slab with—

28 mm metal furring channels and isolation mounts fixed to underside of slab, at 600 mm centres; and

65 mm thick polyester insulation with a density of 8 kg/m3, positioned between furring channels; and

one layer of 13 mm plasterboard fixed to furring channels,

has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C8a.

(3) 200 mm thick concrete slab with carpet on underlay has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C8b.

(4) 100 mm thick concrete slab has an Rw + Ctr of not less than 45 and an Rw of not less than 45, if constructed as shown in Figure S28C8c.

Figure S28C8a 150 mm thick concrete slab

Figure S28C8b 200 mm thick concrete slab with carpet on underlay

Figure S28C8c 100 mm thick concrete slab

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S28C8.