S28C8 Acceptable forms of construction for floors — concrete
Specification 28 Sound insulation for building elements · NCC 2019: Spec F5.2: Table 3
(1) Acceptable forms of construction for concrete floors are set out in (2) to (4).
(2) 150 mm thick concrete slab with—
28 mm metal furring channels and isolation mounts fixed to underside of slab, at 600 mm centres; and
65 mm thick polyester insulation with a density of 8 kg/m3, positioned between furring channels; and
one layer of 13 mm plasterboard fixed to furring channels,
has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C8a.
(3) 200 mm thick concrete slab with carpet on underlay has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C8b.
(4) 100 mm thick concrete slab has an Rw + Ctr of not less than 45 and an Rw of not less than 45, if constructed as shown in Figure S28C8c.
Figure S28C8a 150 mm thick concrete slab
Figure S28C8b 200 mm thick concrete slab with carpet on underlay
Figure S28C8c 100 mm thick concrete slab