S31C13 Smoke-and-heat vents

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.7

Open S31C13 on NCC Online ↗

Notwithstanding S31C12, automatic vents complying with AS 2665 may be used, except where a Class 6 part of a building adjoins the atrium, in lieu of exhaust fans provided that—

the height from the atrium floor to the bottom of the highest vent is not more than 12 m; and

the vents are fitted with a remote manual operation switch located adjacent to the sprinkler control valves or incorporated in the Fire Indicator Panel.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S31C13.