Specification clause · NCC 2022 Volume One
S31C13 Smoke-and-heat vents
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.7
Notwithstanding S31C12, automatic vents complying with AS 2665 may be used, except where a Class 6 part of a building adjoins the atrium, in lieu of exhaust fans provided that—
the height from the atrium floor to the bottom of the highest vent is not more than 12 m; and
the vents are fitted with a remote manual operation switch located adjacent to the sprinkler control valves or incorporated in the Fire Indicator Panel.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S31C13.