S31C18 Alarm systems
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 4.4
(1) A break-glass fire alarm point must be provided at each door to a fire-isolated stairway, fire-isolated ramp or fire-isolated passageway.
(2) A staged alarm must be provided where an air sampling type smoke detection system is provided for the atrium, and must operate as follows:
Alert building management when abnormal smoke levels of 0.03% obscuration per metre are detected.
Initiate a second alarm to management and start all smoke control systems including pressurisation of escape routes when smoke levels of 0.07% obscuration per metre are detected.
Automatically call the fire brigade, activate the emergency warning and intercom system, and de-activate all plant not necessary for fire safety within the building when smoke levels of 0.09% obscuration per metre are detected.
(3) Beam and point type smoke detectors required must simultaneously operate all functions referred to above and activate at the level set out in AS 1670.1.