S31C17 Smoke detection in spaces separated from the atrium by bounding walls

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 4.3

Open S31C17 on NCC Online ↗

Smoke detection systems must be located at all return and relief air openings associated with the building air-handling systems and be—

of the sampling type system as required in S31C16; or

of the point type photoelectric smoke detector.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S31C17.