Specification clause · NCC 2025 Volume One
S31C6 Stop valves
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 2.5
(1) Basic sprinkler and wall wetting systems protecting a building containing an atrium must be provided with easily accessible and identified stop valves.
(2) Sprinkler and wall wetting systems must be provided with independent stop valves.
(3) Sprinkler heads protecting the roof of the atrium must be provided with a stop valve.
(4) Stop valves to wall wetting and roof sprinklers may be of the gate type.
(5) All sprinkler and wall wetting stop valves must be monitored to detect unauthorised closure.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S31C6.