S31C6 Stop valves

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 2.5

Open S31C6 on NCC Online ↗

(1) Basic sprinkler and wall wetting systems protecting a building containing an atrium must be provided with easily accessible and identified stop valves.

(2) Sprinkler and wall wetting systems must be provided with independent stop valves.

(3) Sprinkler heads protecting the roof of the atrium must be provided with a stop valve.

(4) Stop valves to wall wetting and roof sprinklers may be of the gate type.

(5) All sprinkler and wall wetting stop valves must be monitored to detect unauthorised closure.