S37C5 Solar admittance — Method 1 (Single Aspect)

Specification 37 Calculation of U-Value and solar admittance · NCC 2019: Spec J1.5a: 5

Open S37C5 on NCC Online ↗

(1) The solar admittance of a wall-glazing construction must be calculated in accordance with the following formula:

[formula] (2) In the formula at (1)—

[formula] = the wall-glazing construction solar admittance; and

[formula] = the area of each glazing element; and

[formula] = the shading multiplier for each glazing element in accordance with S37C7; and

[formula] = the total system SHGC of each glazing element; and

[formula] = the total wall-glazing construction area.

Changed since NCC 2022. See NCC 2022 Volume One S37C5, or show what changed.

(1) The solar admittance of a wall-glazing construction must be … glazing element; and [formula] = the total wall-glazing construction area. (3) The solar admittance of the wall-glazing construction must not exceed the applicable value in J4D6(5).