Specification clause · NCC 2025 Volume One

S40C3 Time switch

Specification 40 Lighting and power control devices · NCC 2019: Spec J6: 3

Open S40C3 on NCC Online ↗

(1) A time switch must—

be capable of switching on and off electric power at variable pre-programmed times and on variable pre-programmed days; and

have the ability to program public holidays at least 1 year ahead.

(2) A time switch for internal lighting must be capable of being overridden by—

a demand-operated control; or

a manual switch.

(3) A time switch for external lighting must be capable of being configured to limit the period the system is switched on to between 30 minutes before sunset and 30 minutes after sunrise.

(4) A time switch for boiling water or chilled water storage units must be capable of being overridden for a maximum period of 2 hours outside normal operating hours.

Changed since NCC 2022. See NCC 2022 Volume One S40C3, or show what changed.

(1) A time switch must — be — capable of switching on and off electric power at variable pre-programmed times and on variable pre-programmed days; and configured so that have the lights are switched off ability to program public holidays at any time the space is designated to be unoccupied. least 1 year ahead. (2) A time switch for internal lighting must be capable of being overridden by — a means of turning the lights on, either by — demand-operated control; or a manual switch, remote control or an occupant sensing device that on sensing a person’s presence, overrides the time switch for a period of up to 2 hours, after which if there is no further presence detected, the time switch must resume control; or an occupant sensing device that overrides the time switch upon a person’s entry and returns control to the time switch upon the person’s exiting, such as a security card reader or remote control; and a manual “off” switch. (3) A time switch for external lighting must be — capable of being configured to limit the period the system is switched on to between 30 minutes before sunset and 30 minutes after sunrise is determined or detected including any pre-programmed period between these times; and capable of being overridden by a manual switch, remote control or a security access system for a period of up to 8 hours, after which the time switch must resume control. sunrise. (4) A time switch for boiling water or chilled water storage units must be capable of being overridden by a manual switch or a security access system that senses a person’s presence, overrides for a maximum period of up to 2 hours, after which if there is no further presence detected, the time switch must resume control. hours outside normal operating hours.