S40C5 Daylight sensor and dynamic lighting control device
Specification 40 Lighting and power control devices · NCC 2019: Spec J6: 5
A daylight sensor and dynamic control device for artificial lighting must, in response to the measured level of available daylight in the range 50–1000 lux—
for high pressure discharge lights, switch lights on and off with a programmable delay and switching differential; and
for all other lights, dim continuously or step lighting output down in not less than 4 steps so that the lowest power setting is less than 50% of full power.
Changed since NCC 2022. See NCC 2022 Volume One S40C5, or show what changed.
(1) A daylight sensor and dynamic control device for artificial lighting must must, in response to the measured level of available daylight in the range 50–1000 lux — for switching high pressure discharge lights, switch lights on and off — be capable of having the with a programmable delay and switching level set point adjusted between 50 and 1000 lux; and have — a delay of more than 2 minutes; and a differential of more than 100 lux for a sensor controlling high pressure discharge lighting, and 50 lux for a sensor controlling other than high pressure discharge lighting; differential; and for dimmed all other lights, dim continuously or stepped switching, be capable of reducing the power consumed by the controlled step lighting output down in proportion to the incident daylight on the working plane either — continuously down to a power consumption that is less than 50% of full power; or in no not less than 4 steps down to a so that the lowest power consumption that setting is less than 50% of full power. (2) Where a daylight sensor and dynamic control device has a manual override switch, the manual override switch must not be able to switch the lights permanently on or bypass the lighting controls.
Removed words are struck through; added words are highlighted. Comparison of the text only.