S43C5 Separation from hazards
Specification 43 Bushfire protection for certain Class 9 buildings
The external walls and roof of the building must be protected from potential hazards on the site such as liquefied petroleum gas bottles, fuel storage, storage of combustible materials, waste bins, vehicles, machinery, and the like, by—
a separation distance of not less than 10 m; or
where within the 10 m separation distance described in (a), constructed with external walls that have an FRL of not less than 60/60/60 when tested from the outside, including any openings protected in accordance with AS 3959 for BAL—19 or greater; or
for external walls and roof, using a material or system that satisfies the test criteria of AS 1530.8.1 for a radiant heat flux of 10 kW/m² or greater.