NCC 2025 Volume One
Specification 43 Bushfire protection for certain Class 9 buildings
15 clauses · Open on NCC Online ↗
- S43C1 ScopeThis Specification sets out bushfire protection measures for buildings described in G5D4. (2) Compliance with this Specification does not guarantee…
- Table S43C2 Minimum distance of building to classified vegetationVegetation classification | Slope | Minimum distance (m) of the building to classified vegetation High risk | Upslope and flat land | 60 High risk |…
- S43C2 Separation from classified vegetation NSWThe building must be separated from classified vegetation— by not less than the minimum distances specified in Table S43C2; or such that radiant…
- S43C3 Separation between buildingsThe building must be located not less than 12 m from any other building. (2) The separation distance required by (1) need not be complied with if…
- S43C4 Separation from allotment boundaries and carparking areasThe building must be located not less than 10 m from any allotment boundary or open carparking area/spots. (2) The separation distance required by…
- S43C5 Separation from hazardsThe external walls and roof of the building must be protected from potential hazards on the site such as liquefied petroleum gas bottles, fuel…
- S43C6 Non-combustible path around buildingA non-combustible pathway directly adjacent to the building and not less than 1.5 m wide must be provided around the perimeter of the building.
- S43C7 Access pathwaysAccess pathways that lead to a road or open space must— be readily identifiable; and have an even surface; and have a minimum clear width of not…
- S43C8 Exposed external areasAn external area designed to hold people unable to be safely accommodated within the building, that may be exposed to radiant heat flux from a fire…
- S43C9 Internal tenabilityTo maintain internal tenability throughout the duration of occupancy during a bushfire event, the building must comply with the following: An air…
- S43C10 Building envelopeThe building envelope must be constructed in accordance with AS 3959 – BAL 19 or greater, except that where the use of combustible materials is…
- S43C11 Supply of water for fire-fighting purposes NSWWater for fire-fighting purposes must be available and consist of— a fire hydrant system complying with E1D2, or a static water supply consisting of…
- S43C12 Emergency power supplyEmergency power must be provided to support, for not less than 4 hours before and 2 hours after the passing of the fire front during a bushfire…
- S43C13 SignageSignage must be provided to warn building occupants against storing combustible materials under or adjacent to the building.
- S43C14 Vehicular accessVehicular access to the building must be provided in accordance C3D5(2), as if the building were a large isolated building for the purposes of C3D4.