Specification clause · NCC 2025 Volume One
S48C2 Comparison of zone loads in proposed building and reference building
Specification 48 Comparison of zone loads in proposed building and reference building
(1) The zone load is the sensible heating or cooling effect required to maintain the temperature in each zone within the range specified in S34C3(8).
(2) The loads for each zone in the proposed building and the reference building must be calculated in accordance with the modelling parameters of Specification 34.
(3) A zone of the proposed building is assessable under J1V3(1)(b)(iii) to (v) if it has—
a 98th percentile heating load of at least 10 W/m2: or
a 98th percentile cooling load of at least 40 W/m2.