Specification clause · NCC 2025 Volume One
S4C1 Scope
Specification 4 Design of buildings in cyclonic areas · NCC 2019: Spec B1.2: 1
(1) This specification contains requirements for the design of buildings in cyclonic areas in addition to the requirements of AS/NZS 1170.2.
(2) For the purposes of Specification 4, cyclonic areas are those determined as being located in wind regions B2, C and D in accordance with AS/NZS 1170.2.
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One S4C1, or show what changed.
(1) This specification contains requirements for the design of buildings … areas are those determined as being located in wind regions B2, C and D in accordance with AS/NZS 1170.2.
Removed words are struck through; added words are highlighted. Comparison of the text only.