Table S4C2 Low-high-low pressure sequence

Specification 4 Design of buildings in cyclonic areas

Open Table S4C2 on NCC Online ↗
SequenceNumber of cyclesLoad
A45000 to 0.45 Pt
B6000 to 0.6 Pt
C800 to 0.8 Pt
D10 to 1.0 Pt
E800 to 0.8 Pt
F6000 to 0.6 Pt
G45000 to 0.45 Pt

Table Notes

Pt is the ultimate limit state wind pressure on internal and external surfaces as determined in accordance with AS/NZS 1170.2, modified by an appropriate factor for variability, as determined in accordance with Table B1 of AS/NZS 1170.0.

The rate of load cycling must be less than 3 Hz.

The single load cycle (sequence D) must be held for a minimum of 10 seconds.

Table for S4C2 Roof cladding

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S4C2.