Specification clause · NCC 2025 Volume One

S6C3 Walls of certain Class 9b buildings

Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 3.1

Open S6C3 on NCC Online ↗

(1) Lightweight construction forming—

a wall of a lift shaft and stair s haft; and

an external wall and internal wall bounding a public corridor, public lobby or the like, including a fire-isolated and non fire-isolated passageway or ramp,

in spectator stand, sports stadium, cinema or theatre, railway or bus station or airport terminal, must be subjected to the tests and must fulfil the criteria set out in (2).

(2) For the purposes of (1), the following tests and criteria apply:

The materials tests of S6C10(a) and the criteria of S6C11(a).

A static test by the imposition of a uniformly distributed load of 1.0 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.

A dynamic test by the fall of the impact bag through a height of 350 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.

The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).

Changed since NCC 2022 (minor wording). See NCC 2022 Volume One S6C3, or show what changed.

(1) Lightweight construction forming — a wall of a lift shaft and stair shaft; s haft; and an external wall and internal wall bounding a public corridor, public lobby or … test of S6C10(d) and the surface indentation criterion of S6C11(e).

Removed words are struck through; added words are highlighted. Comparison of the text only.