S6C3 Walls of certain Class 9b buildings
Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 3.1
(1) Lightweight construction forming—
a wall of a lift shaft and stair shaft; and
an external and internal wall bounding a public corridor, public lobby or the like, including a fire-isolated and non fire-isolated passageway or ramp,
in spectator stand, sports stadium, cinema or theatre, railway or bus station or airport terminal, must be subjected to the tests and must fulfil the criteria set out in (2).
(2) For the purposes of (1), the following tests and criteria apply:
The materials tests of S6C10(a) and the criteria of S6C11(a).
A static test by the imposition of a uniformly distributed load of 1.0 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.
A dynamic test by the fall of the impact bag through a height of 350 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.
The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).
Changed in NCC 2025 (minor wording). See NCC 2025 Volume One S6C3, or show what changed.