S7C4 Wall and ceiling linings
Specification 7 Fire hazard properties · NCC 2019: Spec C1.10: 4
(1) A wall or ceiling lining system must comply with the group number specified in Table S7C4 and for buildings not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 have—
a smoke growth rate index not more than 100; or
an average specific extinction area less than 250 m2/kg.
(2) A group number of a wall or ceiling lining and the smoke growth rate index or average specific extinction area must be determined by an Accredited Testing Laboratory in accordance with AS 5637.1.
Notes
Until adoption of the next edition of the NCC, determination need not be undertaken by an Accredited Testing Laboratory.
Table S7C4 Wall and ceiling lining materials (material groups permitted)
Class of building
Fire-isolated exits and fire control rooms
Public corridors
Specific areas
Other areas
Class 2 or 3, unsprinklered, excluding accommodation for the aged, people with disabilities and children
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Class 2 or 3, sprinklered, excluding accommodation for the aged, people with disabilities and children
Walls: 1
Walls: 1, 2, 3
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Class 3 or 9a, unsprinklered, accommodation for the aged, people with a disability, children and health-care buildings
Walls: 1
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2, 3
Class 3 or 9a, sprinklered, accommodation for the aged, people with a disability, children and health-care buildings
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Class 5, 6, 7, 8 or 9b schools, unsprinklered
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2
Ceilings: 1, 2, 3
Class 5, 6, 7, 8 or 9b schools, sprinklered
Walls: 1
Walls: 1, 2, 3
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Ceilings: 1 ,2, 3
Class 9b other than schools, unsprinklered
Walls: 1
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2, 3
Class 9b other than schools, sprinklered
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Class 9c, sprinklered
Walls: 1
Walls: 1, 2
Walls: 1, 2, 3
Walls: 1, 2, 3
Ceilings: 1
Ceilings: 1, 2
Ceilings: 1, 2, 3
Ceilings: 1, 2, 3
Table Notes
”Sprinklered” means a building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
”Specific areas” means within—
for Class 2 and 3 buildings, a sole-occupancy unit; and
for Class 5 buildings, open plan offices with a minimum floor dimension/floor to ceiling height ratio > 5; and
for Class 6 buildings, shops or other building with a minimum floor dimension/floor to ceiling height ratio > 5; and
for Class 9a health-care buildings, patient care areas; and
for Class 9b theatres and halls, etc, an auditorium; and
for Class 9b schools, a classroom; and
for Class 9c buildings, resident use area.
Tables
Changed since NCC 2022. See NCC 2022 Volume One S7C4, or show what changed.
(1) A wall or ceiling lining system must comply with … rate index or average specific extinction area must be determined by an Accredited Testing Laboratory in accordance with AS 5637.1. Notes Until adoption of the next edition of the NCC, determination need not be undertaken by an Accredited Testing Laboratory. Table S7C4 Wall and ceiling lining materials (material groups permitted) … a classroom; and for Class 9c buildings, resident use area.
Removed words are struck through; added words are highlighted. Comparison of the text only.