New South Wales variation · NCC 2025 Volume One

NSW S7C4 Wall and ceiling linings

NSW Specification 7 Fire hazard properties · varies S7C4 Wall and ceiling linings

Open on NCC Online ↗

Delete clause S7C4 and insert NSW S7C4 as follows:

(1) A wall or ceiling lining system must comply with the group number specified in Table S7C4 and for buildings not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 have—

a smoke growth rate index not more than 100; or

an average specific extinction area less than 250 m2/kg.

(2) A group number of a wall or ceiling lining and the smoke growth rate index or average specific extinction area must be determined by in accordance with AS 5637.1.

Table S7C4 Wall and ceiling lining materials (material groups permitted)

Class of building

Fire-isolated exits and fire control rooms

Public corridors

Specific areas

Other areas

Class 2 or 3, unsprinklered, excluding accommodation for the aged, people with disabilities and children

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Class 2 or 3, sprinklered, excluding accommodation for the aged, people with disabilities and children

Walls: 1

Walls: 1, 2, 3

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Class 3 or 9a, unsprinklered, accommodation for the aged, people with a disability, children and health-care buildings

Walls: 1

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2, 3

Class 3 or 9a, sprinklered, accommodation for the aged, people with a disability, children and health-care buildings

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Class 5, 6, 7, 8 or 9b schools, unsprinklered

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2

Ceilings: 1, 2, 3

Class 5, 6, 7, 8 or 9b schools, sprinklered

Walls: 1

Walls: 1, 2, 3

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Ceilings: 1 ,2, 3

Class 9b other than schools, unsprinklered

Walls: 1

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2, 3

Class 9b other than schools, sprinklered

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Class 9c, sprinklered

Walls: 1

Walls: 1, 2

Walls: 1, 2, 3

Walls: 1, 2, 3

Ceilings: 1

Ceilings: 1, 2

Ceilings: 1, 2, 3

Ceilings: 1, 2, 3

Table Notes

”Sprinklered” means a building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

”Specific areas” means within—

for Class 2 and 3 buildings, a sole-occupancy unit; and

for Class 5 buildings, open plan offices with a minimum floor dimension/floor to ceiling height ratio > 5; and

for Class 6 buildings, shops or other building with a minimum floor dimension/floor to ceiling height ratio > 5; and

for Class 9a health-care buildings, patient care areas; and

for Class 9b theatres and halls, etc, an auditorium; and

for Class 9b schools, a classroom; and

for Class 9c buildings, resident use area.

New in NCC 2025. No NSW S7C4 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause