South Australia variation · NCC 2025 Volume One

SA F2D2 Wet area construction

SA Part F2 Wet areas and overflow protection · varies F2D2 Wet area construction

Open on NCC Online ↗

Delete subclause F2D2(1) and insert SA F2D2(1) as follows:

(1) In a Class 2 and 3 building and a Class 4 part of a building, building elements in wet areas must—

be water resistant or waterproof in accordance with Specification 26, except that—

in any room containing a washing machine, the wall area from finished floor to a minimum of 75 mm above and 75 mm each side of the washing machine tap outlets must be water resistant; and

where a vessel is inset into a bench top in a kitchen, bar area, kitchenette or domestic food and beverage preparation area, the perimeter edges of the vessel must be water resistant for the extent of the vessel; and

penetrations in horizontal surfaces for tap and spout outlets in kitchens, bar areas, kitchenettes or domestic food and beverage preparation areas must be waterproof; and

comply with AS 3740.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One SA F2D2.