NCC 2025 Volume One
South Australia variations
75 SA variations to NCC 2025 Volume One: clauses replaced, added or deleted in South Australia. Search with SA variations.
- SA A6G7 Class 6 buildingsDelete clause A6G7 and insert SA A6G7 as follows: A Class 6 building is a shop or other building for the sale of goods by retail or the supply of…
- SA B1D6 Construction of buildings in flood hazard areasThis clause has deliberately been left blank.
- SA B1P3 Buildings in flood areasThis clause has deliberately been left blank.
- SA C2D1 Deemed-to-Satisfy ProvisionsDelete subclause C2D1(1) and insert SA C2D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements C1P1 to C1P9…
- SA C2D2 Type of construction requiredDelete subclause C2D2(1) and insert SA C2D2(1) as follows: (1) The minimum Type of fire-resisting construction of a building must be determined in…
- SA C3D1 Deemed-to-Satisfy ProvisionsDelete subclause C3D1(1) and insert SA C3D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements C1P1 to C1P9…
- SA C3D16 Class 2 external walls exposed to brush fencesInsert SA clause C3D16 in clause C3D16 as follows: Where the distance between the external wall of a Class 2 building and a brush fence is less than…
- SA C4D1 Deemed-to-Satisfy ProvisionsDelete subclause C4D1(1) and insert SA C4D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements C1P1 to C1P9…
- SA D2D1 Deemed-to-Satisfy ProvisionsDelete subclause D2D1(1) and insert SA D2D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements D1P1 to…
- SA D3D1 Deemed-to-Satisfy ProvisionsDelete subclause D3D1(1) and insert SA D3D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements D1P1 to…
- SA D4D2 General building access requirementsDelete subclause D4D2(4) and insert SA D4D2(4) as follows: (4) For a Class 2 building, access requirements are as follows: Common areas: From a…
- SA D4D5 ExemptionsDelete clause D4D5 and insert SA D4D5 as follows: The following areas are not required to be accessible: An area where access would be inappropriate…
- SA E1D1 Deemed-to-Satisfy ProvisionsDelete subclause E1D1(1) and insert SA E1D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements E1P1 to E1P6…
- SA E2D1 Deemed-to-Satisfy ProvisionsDelete subclause E2D1(1) and insert SA E2D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements E2P1 and…
- SA E4D1 Deemed-to-Satisfy ProvisionsDelete subclause E4D1(1) and insert SA E4D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements E4P1 to E4P3…
- SA F1D1 Deemed-to-Satisfy ProvisionsDelete subclause F1D1(1) and insert SA F1D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements F1P1 and SA…
- SA F1D2 Application of PartDelete subclause F1D2(3) and insert SA F1D2(3) as follows: (3) F1D3 to F1D8, SA F1D9 and F1D10 to F1D15 do not apply to horizontal or near…
- SA F1D8 Damp-proofingDelete subclause F1D8(2) and insert SA F1D8(2) as follows: (2) Damp-proof coursesmust exhibit long term resistance to degradation by dissolved salts…
- SA F1D9 Damp-proofing of floors on the groundDelete clause F1D9 and insert SA F1D9 as follows: (1) If a floor of a room is laid on the ground or on fill, a damp-proofing membrane complying with…
- SA F1P2 Rising dampInsert SA clause F1P2 in clause F1P2 as follows: (1) Moisture from the ground must be prevented from causing— undue dampness or deterioration of…
- SA F2D1 Deemed-to-Satisfy ProvisionsDelete subclause F2D1(1) and insert SA F2D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements F2P1, F2P2…
- SA F2D2 Wet area constructionDelete subclause F2D2(1) and insert SA F2D2(1) as follows: (1) In a Class 2 and 3 building and a Class 4 part of a building, building elements in…
- SA F2D4 Provision of floor wastesDelete clause F2D4 and insert SA F2D4 as follows: (1) A wet area provided with a vessel in accordance with F4D2, F4D4 and F4D5 must have the floor…
- SA F2P1 Wet area overflowsDelete clause F2P1 and insert SA F2P1 as follows: Overflow from a bathroom, laundry facility or the like must be prevented from penetrating to…
- SA F2P3 Prevention of surface water accumulationInsert SA clause F2P3 in clause F2P3 as follows: In laundries, bathrooms or rooms containing shower facilities the floors must be installed in a…
- SA F4D1 Deemed-to-Satisfy ProvisionsDelete subclause F4D1(1) and insert SA F4D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements F4P1 to F4P6…
- SA F4D6 Accessible unisex sanitary compartmentsDelete subclause F4D6(1) and insert SA F4D6(1) as follows: (1) Where required by F4D5(a), the minimum number of accessible unisex sanitary…
- SA F4D7 Accessible unisex showersDelete subclause F4D7(1) and insert SA F4D7(1) as follows: (1) Where required by F4D5(b), the minimum number of accessible unisex showers for each…
- SA F5D1 Deemed-to-Satisfy ProvisionsDelete subclause F5D1(1) and insert SA F5D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirement F5P1 is…
- SA F6D1 Deemed-to-Satisfy ProvisionsDelete subclause F6D1(1) and insert SA F6D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements F6P1 to F6P5…
- SA G1D1 Deemed-to-Satisfy ProvisionsDelete subclause G1D1(1) and insert SA G1D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements G1P1, SA…
- SA G1D2 Swimming poolsInsert SA subclause G1D2(3) in clause G1D2 as follows: (3) For the purposes of clause 6.1.1 of AS 1926.3, a skimmer box is an outlet, and must have…
- SA G1P2 Swimming pool access and water recirculation systemsDelete clause G1P2 and insert SA G1P2 as follows: (1) A barrier must be provided to a swimming pool and must— be continuous for the full extent of…
- SA G5D1 Deemed-to-Satisfy ProvisionsDelete subclause G5D1(1) and insert SA G5D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements G5P1 and…
- SA G5D5 Bushfire attack levelsInsert SA clause G5D5 in clause G5D5 as follows: Where a site is located in a designated bushfire prone area, the bushfire attack level that applies…
- SA G7D2 Livable housing designDelete clause G7D2 and insert SA G7D2 as follows: (1) Each sole-occupancy unit in a Class 2 building must comply with the ABCB Standard for Livable…
- SA G8D1 Deemed-to-Satisfy ProvisionsDelete clause G8D1 and insert SA G8D1 as follows: Performance Requirements SA G8P1 and SA G8P2 are satisfied by complying with SA G8D2 to SA G8D4.
- SA G8D2 Application of PartDelete clause G8D2 and insert SA G8D2 as follows: SA G8D3 and SA G8D4 apply to Class 2 to 9 buildings.
- SA G8D3 Access for window cleaningDelete clause G8D3 and insert SA G8D3 as follows: (1) Where any part of a window in a building is more than 5.5 m above ground level, access to the…
- SA G8D4 Access for inspection and maintenance between buildingsDelete clause G8D4 and insert SA G8D4 as follows: Every part of an external wall of a building must be not less than 600 mm from— the external wall…
- SA G8F1 Window cleaningDelete clause G8F1 and insert SA G8F1 as follows: A building is to provide people with safe conditions for carrying out window cleaning operations.
- SA G8F2 Hazardous conditionsDelete clause G8F2 and insert SA G8F2 as follows: The space between buildings must not allow hazardous conditions to arise due to accumulation of…
- SA G8O1 ObjectiveDelete clause G8O1 and insert SA G8O1 as follows: The Objectives of this Part are— to safeguard people from injury while cleaning windows; and to…
- SA G8P1 Window cleaningDelete clause G8P1 and insert SA G8P1 as follows: Where any part of a window in a building is more than 5.5 m above ground level, provision must be…
- SA G8P2 Hazardous conditionsDelete clause G8P2 and insert SA G8P2 as follows: The space between buildings must be sufficient to allow access for inspection and maintenance, to…
- SA G9D1 Deemed-to-Satisfy ProvisionsDelete clause G9D1 and insert SA G9D1 as follows: Performance Requirement SA G9P1 is satisfied by complying with SA G9D2 and SA G9D3.
- SA G9D2 Application of PartDelete clause G9D2 and insert SA G9D2 as follows: SA G9D3 applies to Class 2 to 9 buildings.
- SA G9D3 Attachments to buildingsDelete clause G9D3 and insert SA G9D3 as follows: (1) An attachment to a building that is in the nature of a balcony or awning, bridge, gangway,…
- SA G9P1 Attachments to buildingsDelete clause G9P1 and insert SA G9P1 as follows: An attachment to a building must incorporate features that will— protect it against corrosion; and…
- SA I3D1 Application of PartDelete clause I3D1 and insert SA I3D1 as follows: (1) The Deemed-to-Satisfy Provisions of this Part apply to farm buildings in South Australia. (2)…
- SA I3D2 Fire resistance and separationThis clause has deliberately been left blank.
- SA I3D3 Provision for escapeDelete clause I3D3 and insert SA I3D3 as follows: (1) Exit travel distances in a farm building must comply with D2D5 except— no point on the floor…
- SA I3D4 Construction of exitsThis clause has deliberately been left blank.
- SA I3D5 Fixed platforms, walkways, stairways and laddersDelete clause I3D5 and insert SA I3D5 as follows: A fixed platform, stairway, ladder and any going and riser, landing, handrail or barrier may…
- SA I3D8 Fire fighting equipmentThis clause has deliberately been left blank.
- SA I3D9 Fire hydrants and water suppliesDelete clause I3D9 and insert SA I3D9 as follows: (1) A farm building need not be provided with a fire hydrant system in accordance with E1D2, if it…
- SA I3D10 Fire hose reelsDelete clause I3D10 and insert SA I3D10 as follows: E1D3 does not apply to a farm building except when it is used for hay storage exceeding 500 m2…
- SA I3D11 Portable fire extinguishersDelete clause I3D11 and insert SA I3D11 as follows: (1) For Class A fire risks in a farm building the requirements of E1D14 need not be provided if—…
- SA I3D12 Emergency lighting requirementsDelete clause I3D12 and insert SA I3D12 as follows: An emergency lighting system complying with E4D2 must be installed in a farm building except…
- SA I3D13 Exit signsDelete clause I3D13 and insert SA I3D13 as follows: An exit sign must be clearly visible to persons approaching the exit, and must be installed on,…
- SA I3D14 Direction signsDelete clause I3D14 and insert SA I3D14 as follows: In a farm building, if an exit is not readily apparent to persons occupying or visiting the…
- SA I3D15 Design and operation of exit signsDelete clause I3D15 and insert SA I3D15 as follows: In a farm building, each required exit sign provided under E4D5, SA I3D13 and SA I3D14 need not…
- SA I3D16 Sanitary facilitiesThis clause has deliberately been left blank.
- SA I3D17 Height of rooms and other spacesThis clause has deliberately been left blank.
- SA I3D18 Artificial lightingDelete clause I3D18 and insert SA I3D18 as follows: An artificial lighting system need not be provided in a farm building where— occupants are…
- SA I4D1 Application of PartDelete clause I4D1 and insert SA I4D1 as follows: (1) The Deemed-to-Satisfy Provisions of this Part apply to bulk grain storage facilities in South…
- SA I4D2 Type of construction requiredDelete clause I4D2 and insert SA I4D2 as follows: The external walls of a bulk grain storage facility need not be of fire-resisting construction in…
- SA I4D3 CompartmentationDelete clause I4D3 and insert SA I4D3 as follows: Underground passageways in a bulk grain storage facility must be separated from other parts of the…
- SA I4D4 Protection of openingsDelete clause I4D4 and insert SA I4D4 as follows: Where external stairs, ramps or ladders are used as an exit in a bulk grain storage facility — any…
- SA I4D5 Provision for escapeDelete clause I4D5 and insert SA I4D5 as follows: (1) In addition to any horizontal exit, not less than 2 exits must be provided from— a storage…
- SA I4D6 Fire hydrants and water suppliesDelete clause I4D6 and insert SA I4D6 as follows: (1) A bulk grain storage facility need not provide an on-site fire hydrant system in accordance…
- SA I4D7 Fire hose reelsDelete clause I4D7 and insert SA I4D7 as follows: E1D3 does not apply to a bulk grain storage facility.
- SA I4D8 Smoke ventingDelete clause I4D8 and insert SA I4D8 as follows: (1) In a bulk grain storage facility, suitable natural smoke venting by fixed vents must be…
- SA I4D9 Emergency lighting requirementsDelete clause I4D9 and insert SA I4D9 as follows: (1) An emergency lighting system complying with E4D2 must be installed in a bulk grain storage…
- SA I4D10 VentilationDelete clause I4D10 and insert SA I4D10 as follows: In a bulk grain storage facility, a habitable room, office, shop, factory, workroom, sanitary…