South Australia variation · NCC 2025 Volume One

SA G5D5 Bushfire attack levels

SA Part G5 Construction in bushfire prone areas

Open on NCC Online ↗

Insert SA clause G5D5 in clause G5D5 as follows:

Where a site is located in a designated bushfire prone area, the bushfire attack level that applies to the site is—

for areas identified as general bushfire risk areas in the Planning and Design Code, the BAL-Low bushfire attack level; and

for areas identified as medium bushfire risk areas in the Planning and Design Code, the BAL-12.5 bushfire attack level; and

for areas identified as high bushfire risk areas in the Planning and Design Code, the bushfire attack level assessed for the site in accordance with the requirements of AS 3959; and

for areas identified as urban interface in the Planning and Design Code that are within 500 m of a high bushfire risk area, the BAL-Low bushfire attack level; and

for areas identified as urban interface in the Planning and Design Code that are within 100 m of a high bushfire risk area, the bushfire attack level assessed for the site in accordance with AS 3959.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One SA G5D5.