South Australia variation · NCC 2025 Volume One

SA G8D3 Access for window cleaning

SA Part G8 Access for maintenance

Open on NCC Online ↗

Delete clause G8D3 and insert SA G8D3 as follows:

(1) Where any part of a window in a building is more than 5.5 m above ground level, access to the external surface of the window for minor maintenance and cleaning must be provided.

(2) Any of the following methods are acceptable—

by means of a movable gantry; or

by means of reversible pivoting sashes, each of which has catches that secure the mesh in either the normal or reversed position and give visual indication that the window is secure, provided that where a window sill is less than 900 mm above floor level, safety anchorages are provided; or

by means of safety harness, having all anchorages—

designed and installed in accordance with AS/NZS 1891.4; and

constructed of approved corrosion resistant material; or

by means of opening sashes, in which the maximum reach to the farthest part of the window must not exceed 500 mm upwards or 1 m sideways or downwards and provided that where the window sill is less than 900 mm above floor level, safety anchorages are provided.

Changed since NCC 2022. See NCC 2022 Volume One SA G8D3, or show what changed.