Table J3D11c Orientation sector winter exposure factor (EW): climate zone 3

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D11c on NCC Online ↗
P/HNorthNorth eastEastSouth eastSouthSouth westWestNorth west
0.000.901.100.880.690.500.580.670.91
0.050.891.060.820.600.440.510.640.89
0.100.831.010.780.580.420.490.610.84
0.200.740.900.700.520.400.440.550.76
0.400.590.740.600.430.360.370.470.63
0.600.440.570.480.390.340.320.380.51
0.800.300.450.430.340.300.300.320.41
1.000.200.380.350.300.280.280.290.33
1.200.140.290.310.280.280.250.240.28
1.400.110.260.250.260.260.230.210.24
1.600.080.230.240.240.240.210.200.20
1.800.070.160.190.240.240.190.170.18
2.000.060.160.180.210.240.190.150.16

Table for J3D11 External winter glazing of a Class 4 part of a building