Table J3D14c Heated water load factor for a Class 4 part of a building

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D14c on NCC Online ↗
Total floor area m2Load factorTotal floor area m2Load factorTotal floor area m2Load factorTotal floor area m2Load factor
< 500.20160 - 1690.48280 - 2890.59400 - 4090.66
50 - 590.22170 - 1790.49290 - 2990.60410 - 4190.67
60 - 690.25180 - 1890.51300 - 3090.60420 - 4290.67
70 - 790.28190 - 1990.52310 - 3190.61430 - 4390.68
80 - 890.31200 - 2090.53320 - 3290.61440 - 4490.69
90 - 990.34210 - 2190.54330 - 3390.62450 - 4590.69
100 - 1090.37220 - 2290.55340 - 3490.62460 - 4690.70
110 - 1190.39230 - 2390.56350 - 3590.63470 - 4790.71
120 - 1290.41240 - 2490.56360 - 3690.63480 - 4890.72
130 - 1390.43250 - 2590.57370 - 3790.64490 - 4990.72
140 - 1490.45260 - 2690.58380 - 3890.655000.73
150 - 1590.47270 - 2790.58390 - 3990.65——

Table Notes

The total floor area is measured within the inside face of the external walls of the sole-occupancy unit and includes any conditioned attached Class 10a building.

Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.

Table for J3D14 Net equivalent energy usage of a Class 4 part of a building

New in NCC 2025. No Table J3D14c in NCC 2022 Volume One; it may have moved or been renumbered.