Table · NCC 2025 Volume One
Table J3D14c Heated water load factor for a Class 4 part of a building
Part J3 Elemental provisions for a Class 4 part of a building
| Total floor area m2 | Load factor | Total floor area m2 | Load factor | Total floor area m2 | Load factor | Total floor area m2 | Load factor |
|---|---|---|---|---|---|---|---|
| < 50 | 0.20 | 160 - 169 | 0.48 | 280 - 289 | 0.59 | 400 - 409 | 0.66 |
| 50 - 59 | 0.22 | 170 - 179 | 0.49 | 290 - 299 | 0.60 | 410 - 419 | 0.67 |
| 60 - 69 | 0.25 | 180 - 189 | 0.51 | 300 - 309 | 0.60 | 420 - 429 | 0.67 |
| 70 - 79 | 0.28 | 190 - 199 | 0.52 | 310 - 319 | 0.61 | 430 - 439 | 0.68 |
| 80 - 89 | 0.31 | 200 - 209 | 0.53 | 320 - 329 | 0.61 | 440 - 449 | 0.69 |
| 90 - 99 | 0.34 | 210 - 219 | 0.54 | 330 - 339 | 0.62 | 450 - 459 | 0.69 |
| 100 - 109 | 0.37 | 220 - 229 | 0.55 | 340 - 349 | 0.62 | 460 - 469 | 0.70 |
| 110 - 119 | 0.39 | 230 - 239 | 0.56 | 350 - 359 | 0.63 | 470 - 479 | 0.71 |
| 120 - 129 | 0.41 | 240 - 249 | 0.56 | 360 - 369 | 0.63 | 480 - 489 | 0.72 |
| 130 - 139 | 0.43 | 250 - 259 | 0.57 | 370 - 379 | 0.64 | 490 - 499 | 0.72 |
| 140 - 149 | 0.45 | 260 - 269 | 0.58 | 380 - 389 | 0.65 | 500 | 0.73 |
| 150 - 159 | 0.47 | 270 - 279 | 0.58 | 390 - 399 | 0.65 | — | — |
Table Notes
The total floor area is measured within the inside face of the external walls of the sole-occupancy unit and includes any conditioned attached Class 10a building.
Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.
Table for J3D14 Net equivalent energy usage of a Class 4 part of a building
New in NCC 2025. No Table J3D14c in NCC 2022 Volume One; it may have moved or been renumbered.