J3D14 Net equivalent energy usage of a Class 4 part of a building
Part J3 Elemental provisions for a Class 4 part of a building
(1) The net equivalent energy usage of a Class 4 part of a building must not exceed the allowance determined in accordance with the following formula:
[formula] , where—
[formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and
[formula] = the energy factor obtained from Table J3D14b.
(2) For the purposes of (1), the net equivalent energy usage must be calculated—
where the Class 4 part of a building is served by a dedicated heated water system, in accordance with (3); and
where the Class 4 part of a building is served by a centralised heated water system, in accordance with (4).
(3)
The net equivalent energy usage of a Class 4 part of a building served by a dedicated heated water system must be determined in accordance with the following formula: [formula] , where—
[formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and
[formula] = the main space conditioning and main water heater efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors; and
[formula] = the swimming pool pump energy usage in (5); and
[formula] = the spa pump energy in (6); and
[formula] = the installed capacity of a on-site photovoltaics apportioned to the Class 4 part of a building (kW); and
(4)
The net equivalent energy usage of a Class 4 part of a building served by a centralised heated water system must be determined in accordance with the following formula: [formula] , where—
[formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and
[formula] = subject to (7), the main space conditioning and main water heater efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors; and
[formula] = the swimming pool pump energy usage in (5); and
[formula] = the spa pump energy usage in (6); and
[formula] = the centralised heated water system circulating pump energy usage in (8); and
[formula] = the installed capacity, in kW, of on-site photovoltaics apportioned to the Class 4 part of a building; and
[formula] = the installed capacity, in kW, of on-site photovoltaics that directly offsets the energy consumption of circulating pumps for a centralised heated water system serving a Class 4 part of a building, where—
this value does not exceed circulating pump energy usage [formula] ; and
the on-site solar photovoltaics are directly connected to the same electrical supply as common area equipment in the building, including the circulating pumps.
(5)
The swimming pool pump energy usage (EP) for a swimming pool dedicated solely to the Class 4 part of a building must be determined in accordance with the following formula: [formula] , where—
[formula] = the swimming pool pump energy usage; and
[formula] = the volume of the swimming pool to the nearest 1000 litres; and
[formula] = the swimming pool pump factor in Table 13.6.2c of the ABCB Housing Provisions.
(6)
The spa pump energy usage (ES) must be determined in accordance with the following formula: [formula] ,where—
[formula] = the spa pump energy usage; and
[formula] = the volume of the spa to the nearest 100 litres; and
[formula] = the spa pump factor in Table 13.6.2d of the ABCB Housing Provisions.
(7) The main space conditioning and main water heater efficiency factor for a Class 4 part of a building served by a centralised heated water system must be determined in accordance with the following—
for other than a solar boosted centralised heated water system, the equivalent water heater used to the determine the efficiency factor in the ABCB Standard for Whole-of-Home Efficiency Factors must be determined in accordance with Table J3D14e; and
for a solar boosted centralised heated water system, the efficiency factors must be determined in accordance with the following formula: [formula] , where—
[formula] = the main space conditioning and main water heater efficiency factor; and
[formula] = the efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors using the equivalent water heater in Table J3D14e; and
[formula] = the efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors for—
where the solar boosted centralised heated water system uses heat pump type heating as the auxiliary heating source, a heat pump (standard) water heater; and
where the solar boosted centralised heated water system uses gas type heating as the auxiliary heating source, a gas storage water heater; and
for all other types of solar boosted centralised heated water systems, an electric storage (standard) water heater; and
[formula] = the solar percentage factor determined in accordance with the following formula: [formula] , where—
[formula] = the solar percentage factor; and
[formula] = the total area in m2 of all solar thermal collectors connected to the heated water system; and
[formula] = the total floor area in m2 of all sole-occupancy units served by the heated water system.
[formula] = the non-solar percentage factor determined in accordance with the following formula: [formula] , where—
[formula] = the non-solar percentage factor; and
[formula] = the solar percentage factor in (iv); and
where the main space conditioning and main water heater efficiency factor for the heat pump [formula] is less than that of the solar boosted system [formula] then [formula] must be set to 0 and [formula] to 1; and
[formula] cannot be greater than 1.0.
(8)
The circulating pump energy usage [formula] must be determined in accordance with the following formula: [formula] , where—
[formula] = the circulating pump energy usage; and
[formula] = heated water load factor obtained from Table J3D14c; and
[formula] = the primary circulating pump energy factor obtained from Table J3D14d; and
[formula] = the secondary circulating pump energy factor obtained from Table J3D14d; and
[formula] = the factor for the number of sole-occupancy units served determined in accordance with the following formula: [formula] = 0.6 + (number of sole-occupancy units served - 100) x 0.00133; and
[formula] = cannot be greater than 1.0.
Table J3D14a Floor area adjustment factor for a Class 4 part of a building
Total floor area m2
Floor area factor
Total floor area m2
Floor area factor
Total floor area m2
Floor area factor
Total floor area m2
Floor area factor
< 50
0.0123
160–169
0.0097
280–289
0.0087
400–409
0.0080
50–59
0.0119
170–179
0.0096
290–299
0.0086
410–419
0.0079
60–69
0.0116
180–189
0.0095
300–309
0.0085
420–429
0.0079
70–79
0.0113
190–199
0.0094
310–319
0.0085
430–439
0.0078
80–89
0.0111
200–209
0.0093
320–329
0.0084
440–449
0.0078
90–99
0.0108
210–219
0.0092
330–339
0.0083
450–459
0.0077
100–109
0.0106
220–229
0.0091
340–349
0.0083
460–469
0.0077
110–119
0.0105
230–239
0.0090
350–359
0.0082
470–479
0.0077
120–129
0.0103
240–249
0.0090
360–369
0.0082
480–489
0.0076
130–139
0.0101
250–259
0.0089
370–379
0.0081
490–499
0.0076
140–149
0.0100
260–269
0.0088
380–389
0.0081
500
0.0075
150–159
0.0099
270–279
0.0087
390–399
0.0080
—
—
Table Notes
The total floor area is measured within the inside face of the external walls of the sole-occupancy unit and includes any conditioned attached Class 10a building.
Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.
Table J3D14b Energy factor for a Class 4 part of a building
Climate zone
ACT
NSW
NT
QLD
SA
TAS
Vic
WA
1
—
—
2.73
3.95
—
—
—
4.64
2
—
1.88
—
2.54
—
—
—
—
3
—
—
1.76
3.52
—
—
—
4.10
4
—
2.57
—
—
2.65
—
1.79
3.34
5
—
2.50
—
3.26
2.56
—
—
3.36
6
—
3.43
—
—
3.58
—
2.32
4.58
7
3.66
3.32
—
—
—
4.41
2.32
—
8
—
5.70
—
—
—
5.60
4.02
—
Table J3D14c Heated water load factor for a Class 4 part of a building
Total floor area m2
Load factor
Total floor area m2
Load factor
Total floor area m2
Load factor
Total floor area m2
Load factor
< 50
0.20
160 - 169
0.48
280 - 289
0.59
400 - 409
Tables
- Table J3D14a Floor area adjustment factor for a Class 4 part of a building
- Table J3D14b Energy factor for a Class 4 part of a building
- Table J3D14c Heated water load factor for a Class 4 part of a building
- Table J3D14d Energy factor (CP or CS) for a circulating pump serving a Class 4 part of a building
- Table J3D14e Water heater type to be applied when using the ABCB Standard for Whole-of-Home Efficiency Factors for a Class 4 part of a building
Changed since NCC 2022. See NCC 2022 Volume One J3D14, or show what changed.
(1) The net equivalent energy usage of a sole-occupancy unit of a Class 2 building or Class 4 part of a building, calculated in accordance with (a), building must not exceed the allowance calculated determined in accordance with (b)— the following formula: [formula] , where — [formula] = the floor area factor obtained from multiplying the total floor area by the adjustment factor in Table J3D14a; and [formula] = the energy factor obtained from Table J3D14b. (2) For the purposes of (1), the net equivalent energy usage must be calculated — where the Class 4 part of a building is served by a dedicated heated water system, in accordance with (3); and where the Class 4 part of a building is served by a centralised heated water system, in accordance with (4). (3) The net equivalent energy usage of a Class 4 part of a building served by a dedicated heated water system must be determined in accordance with the following formula: [formula] , where — [formula] = the floor area factor … and [formula] = the swimming pool pump energy usage in (2); (5); and [formula] = the spa pump energy usage in (3); (6); and [formula] = the installed capacity of a on-site photovoltaics apportioned to the sole-occupancy unit of a Class 2 building or Class 4 part of a building (kW); and (4) The net equivalent energy usage of a Class 4 part of a building served by a centralised heated water system must be determined in accordance with the following formula: [formula] , where — [formula] = the floor area factor … by the adjustment factor in Table J3D14a; and [formula] = subject to (7), the energy main space conditioning and main water heater efficiency factor obtained from Table J3D14b. (2) the ABCB Standard for Whole-of-Home Efficiency Factors; and [formula] = the swimming pool pump energy usage in (5); and [formula] = the spa pump energy usage in (6); and [formula] = the centralised heated water system circulating pump energy usage in (8); and [formula] = the installed capacity, in kW, of on-site photovoltaics apportioned to the Class 4 part of a building; and [formula] = the installed capacity, in kW, of on-site photovoltaics that directly offsets the energy consumption of circulating pumps for a centralised heated water system serving a Class 4 part of a building, where — this value does not exceed circulating pump energy usage [formula] ; and the on-site solar photovoltaics are directly connected to the same electrical supply as common area equipment in the building, including the circulating pumps. (5) The swimming pool pump energy usage (EP) for a swimming pool dedicated solely to the Class 4 part of a building must be determined in accordance with the following formula: [formula] … pump factor in Table 13.6.2c of the ABCB Housing Provisions. (3) (6) The spa pump energy usage (ES) must be determined in … pump factor in Table 13.6.2d of the ABCB Housing Provisions. (7) The main space conditioning and main water heater efficiency factor for a Class 4 part of a building served by a centralised heated water system must be determined in accordance with the following — for other than a solar boosted centralised heated water system, the equivalent water heater used to the determine the efficiency factor in the ABCB Standard for Whole-of-Home Efficiency Factors must be determined in accordance with Table J3D14e; and for a solar boosted centralised heated water system, the efficiency factors must be determined in accordance with the following formula: [formula] , where — [formula] = the main space conditioning and main water heater efficiency factor; and [formula] = the efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors using the equivalent water heater in Table J3D14e; and [formula] = the efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors for — where the solar boosted centralised heated water system uses heat pump type heating as the auxiliary heating source, a heat pump (standard) water heater; and where the solar boosted centralised heated water system uses gas type heating as the auxiliary heating source, a gas storage water heater; and for all other types of solar boosted centralised heated water systems, an electric storage (standard) water heater; and [formula] = the solar percentage factor determined in accordance with the following formula: [formula] , where — [formula] = the solar percentage factor; and [formula] = the total area in m2 of all solar thermal collectors connected to the heated water system; and [formula] = the total floor area in m2 of all sole-occupancy units served by the heated water system. [formula] = the non-solar percentage factor determined in accordance with the following formula: [formula] , where — [formula] = the non-solar percentage factor; and [formula] = the solar percentage factor in (iv); and where the main space conditioning and main water heater efficiency factor for the heat pump [formula] is less than that of the solar boosted system [formula] then [formula] must be set to 0 and [formula] to 1; and [formula] cannot be greater than 1.0. (8) The circulating pump energy usage [formula] must be determined in accordance with the following formula: [formula] , where — [formula] = the circulating pump energy usage; and [formula] = heated water load factor obtained from Table J3D14c; and [formula] = the primary circulating pump energy factor obtained from Table J3D14d; and [formula] = the secondary circulating pump energy factor obtained from Table J3D14d; and [formula] = the factor for the number of sole-occupancy units served determined in accordance with the following formula: [formula] = 0.6 + (number of sole-occupancy units served - 100) x 0.00133; and [formula] = cannot be greater than 1.0. Table J3D14a Floor area adjustment factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building Total floor area … metres of floor area. Table J3D14b Energy factor for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building Climate zone ACT NSW … — 8 — 5.70 — — — 5.60 4.02 — Table J3D14c Heated water load factor for a Class 4 part of a building Total floor area m2 Load factor Total floor area m2 Load factor Total floor area m2 Load factor Total floor area m2 Load factor < 50 0.20 160 - 169 0.48 280 - 289 0.59 400 - 409
Removed words are struck through; added words are highlighted. Comparison of the text only.