Table · NCC 2025 Volume One

Table J3D7n Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 5

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D7n on NCC Online ↗
Roof ventilationReflective insulation under- roofUnder-roof insulation R-ValueSA ≤ 0.42SA > 0.42 to ≤ 0.64
VentedYes< 0.53.02.5
≥ 0.52.5
No0 to < 2.03.0
≥ 2.02.5
StandardYesAny2.5
No0 to < 1.03.0
≥ 1.0 to < 2.02.5
≥ 2.03.0

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for J3D7 Roofs and ceilings of a Class 4 part of a building

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D7n.