Deemed-to-Satisfy Provision · NCC 2025 Volume One

J3D7 Roofs and ceilings of a Class 4 part of a building

Part J3 Elemental provisions for a Class 4 part of a building

Open J3D7 on NCC Online ↗

(1) Roof and ceiling insulation must achieve the minimum R-Value —

in climate zone 1, in accordance with Tables J3D7a, J3D7b and J3D7c as applicable; and

in climate zone 2, in accordance with Tables J3D7d, J3D7e and J3D7f as applicable; and

in climate zone 3, in accordance with Tables J3D7g, J3D7h and J3D7i as applicable; and

in climate zone 4, in accordance with Tables J3D7j, J3D7k and J3D7l as applicable; and

in climate zone 5, in accordance with Tables J3D7m, J3D7n and J3D7o as applicable; and

in climate zone 6—

R3.5; or

if the roof contains reflective insulation, R3.0; and

in climate zones 7 and 8, in accordance with Tables J3D7p, J3D7q and J3D7r as applicable.

(2) Reflective insulation installed to comply with (1) must—

have a surface emittance of not more than 0.05; and

be adjacent to a roof space of not less than 20 mm; and

in climate zones 3 to 8, be downward facing.

(3) The thermal bridging in a metal-framed roof must be addressed as follows—

for a pitched roof with a horizontal ceiling—

achieving the Total R-Value in Table J3D7s, calculated using a method that accounts for the effects of thermal bridging; or

increasing the R-Value of the insulation between the ceiling frames by R0.5 more than the R-Value derived from (1); or

adding a continuous ceiling insulation layer with a minimum R-Value of R0.13 above or below the ceiling joists or the bottom chords of the trusses; or

achieving the required ceiling R-Value derived from (1) by stacking two layers of insulation immediately on top of each other, such that the top layer is orientated to cover the ceiling joists or bottom chord of the trusses and has an R-Value of at least R0.5; or

for a flat, skillion or cathedral roof—

achieving the Total R-Value in Table J3D7t, calculated using a method that accounts for the effects of thermal bridging; or

complying with Table J3D7u.

(4) Where F8D5(1) applies, continuous insulation placed above the primary insulation layer to mitigate thermal bridging must have a vapour permeance of not less than that of the primary insulation layer.

(5) Where, for operational or safety reasons, the area of ceiling insulation required is reduced, the loss of insulation must be compensated for in accordance with Table J3D7w.

(6) Where the ceiling insulation required by (1) to (5) has an R-Value —

greater than R3.0 and less than or equal to R4.5, it may be reduced to R3.0 within 450 mm of an external wall; or

greater than R4.5, it may be reduced to R3.0 within 450 mm of an external wall, provided all other required ceiling insulation is increased by R0.5.

(7) The requirements of (1) to (6) do not apply to roofs constructed using insulated sandwich panels.

(8) Roofs constructed using insulated sandwich panels must achieve the minimum Total R-Value in Table J3D7x.

(9) In climate zones 1 to 5, the solar absorptance of the upper surface of a roof must not be more than 0.64.

Table J3D7a Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 1

Reflective insulation under-roof

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Yes

1.0

1.5

2.0

2.5

3.0

No

1.5

2.0

2.5

3.0

4.0

Table Notes

SA = solar absorptance.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table J3D7b Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 1

Roof ventilation

Reflective insulation under-roof

Under-roof insulation R-Value

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Vented

Yes

< 1.0

1.5

1.5

1.5

1.5

2.0

≥ 1.0 to < 1.5

1.5

1.5

1.5

1.5

1.5

≥ 1.5 to < 2.0

1.5

1.5

1.5

1.5

1.5

≥ 2.0

1.5

1.5

1.5

2.0

2.0

No

< 1.0

2.0

2.5

4.0

5.0

X

≥ 1.0 to < 1.5

1.5

1.5

1.5

1.5

2.5

≥ 1.5 to < 2.0

1.5

1.5

1.5

2.0

2.0

≥ 2.0

1.5

1.5

1.5

1.5

1.5

Standard

Yes

< 1.0

1.5

1.5

2.0

3.0

4.0

≥ 1.0 to < 1.5

1.5

1.5

1.5

1.5

2.5

≥ 1.5 to < 2.0

1.5

1.5

1.5

1.5

2.0

≥ 2.0

1.5

1.5

1.5

1.5

1.5

No

< 1.0

2.5

4.0

6.0

X

X

≥ 1.0 to < 1.5

1.5

1.5

1.5

1.5

4.0

≥ 1.5 to < 2.0

1.5

1.5

2.0

2.0

2.5

≥ 2.0

1.5

1.5

1.5

2.0

2.5

Table Notes

SA = solar absorptance.

A roof space is to be considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Table J3D7c Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 1

Reflective insulation under-roof

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Yes

1.5

1.5

2.0

3.0

4.0

No

1.5

3.5

5.0

X

X

Table Notes

SA = solar absorptance.

The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Table J3D7d Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 2

Reflective insulation under-roof

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Yes

2.0

2.5

2.5

3.0

3.5

No

3.0

3.0

3.5

4.0

4.5

Table Notes

SA = solar absorptance.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table J3D7e Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 2

Roof ventilation

Reflective insulation under-roof

Under-roof insulation R-Value

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Vented

Yes

Any

2.5

No

0 to < 0.5

2.5

3.0

3.0

3.5

3.5

≥ 0.5

2.5

Standard

Yes

Any

2.5

No

0 to < 0.5

3.0

3.0

3.5

4.0

4.0

≥ 0.5 to < 1.0

2.5

2.5

2.5

3.0

3.0

≥ 1.0

2.5

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table J3D7f Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 2

Reflective insulation under-roof

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Yes

2.5

2.5

2.5

2.5

2.5

No

3.0

3.0

3.5

4.0

4.0

Table Notes

SA = solar absorptance.

The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table J3D7g Flat concrete roof — minimum R-Value for ceiling insulation: climate zone 3

Reflective insulation under-roof

SA ≤ 0.23

SA > 0.23 to ≤ 0.32

SA > 0.32 to ≤ 0.42

SA > 0.42 to ≤ 0.53

SA > 0.53 to ≤ 0.64

Yes

2.0

2.0

2.5

2.5

3.0

No

3.0

3.5

4.0

4.5

5.0

Table Notes

SA = solar absorptance.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Val

Tables

Changed since NCC 2022. See NCC 2022 Volume One J3D7, or show what changed.

(1) Roof and ceiling insulation must achieve the minimum R-Value … or ceiling insulation. R-Values listed are for the labelled, declared R-Value R-Val

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J3D7? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →