Table J3D7q Timber-framed pitched roof with flat ceiling — minimum R-Value for ceiling insulation: climate zones 7 and 8
Part J3 Elemental provisions for a Class 4 part of a building
| Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 | SA > 0.64 to ≤ 0.73 | SA > 0.73 to ≤ 0.85 | SA > 0.85 |
|---|---|---|---|---|---|---|---|---|---|---|
| Standard | Yes | 0 to < 1.0 | 4.5 | 4.5 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 |
| ≥ 1.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | ||
| No | 0 to < 1.0 | 5.0 | 4.5 | 4.5 | 4.0 | 4.0 | 3.5 | 3.5 | 3.5 | |
| ≥ 1.0 to < 1.5 | 4.5 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | 3.5 | 3.5 | ||
| ≥ 1.5 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | ||
| Vented | Yes | 0 to < 1.0 | 4.5 | 4.5 | 4.5 | 4.5 | 4.5 | 4.0 | 4.0 | 4.0 |
| ≥ 1.0 | 4.5 | 4.5 | 4.5 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | ||
| No | 0 to < 1.0 | 5.0 | 4.5 | 4.5 | 4.5 | 4.0 | 4.0 | 3.5 | 3.5 | |
| ≥ 1.0 to < 1.5 | 4.5 | 4.5 | 4.5 | 4.5 | 4.0 | 4.0 | 4.0 | 4.0 | ||
| ≥ 1.5 | 4.5 | 4.5 | 4.5 | 4.5 | 4.5 | 4.0 | 4.0 | 4.0 |
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or
is ventilated to outdoor air through evenly distributed openings in accordance with Table F8D5; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table for J3D7 Roofs and ceilings of a Class 4 part of a building