Table · NCC 2025 Volume One

Table J3D7x Total R-Values for roofs constructed with insulated sandwich panels

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D7x on NCC Online ↗
Climate zoneSA ≤ 0.23SA > 0.23 to ≤ 0.32SA > 0.32 to ≤ 0.42SA > 0.42 to ≤ 0.53SA > 0.53 to ≤ 0.64SA > 0.64 to ≤ 0.73SA > 0.73 to ≤ 0.85SA > 0.85
11.863.314.32XXXXX
2 – heat flow down3.113.113.313.663.66XXX
2 – heat flow up3.023.023.223.573.57XXX
3 – heat flow down3.313.664.32XXXXX
3 – heat flow up3.223.574.22XXXXX
43.223.223.223.223.22XXX
53.023.023.023.023.02XXX
63.573.573.573.573.573.573.573.57
74.223.903.903.573.573.223.223.22
83.903.573.573.223.223.023.023.02

Table Notes

SA = solar absorptance.

Direction of heat flow must be determined in accordance with Table J3D7v.

X = not permitted.

Table for J3D7 Roofs and ceilings of a Class 4 part of a building

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D7x.

Defined terms used