Table · NCC 2025 Volume One
Table J6D12a Nominal minimum energy efficiency ratio figures for air-cooled unitary air-conditioning systems
Part J6 Air-conditioning and ventilation
| Rated cooling capacity | Unitary systems other than variable refrigerant flow units | Variable refrigerant flow units |
|---|---|---|
| ≤ 39 kW | 3.3 | 3.8 |
| > 39 kW | 3.1 | 3.4 |
Table for J6D12 Unitary air-conditioning equipment
New in NCC 2025. No Table J6D12a in NCC 2022 Volume One; it may have moved or been renumbered.