Deemed-to-Satisfy Provision · NCC 2025 Volume One

J6D12 Unitary air-conditioning equipment

Part J6 Air-conditioning and ventilation · NCC 2019: J5.11

Open J6D12 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) Water-to-air unitary air-conditioners with a rated capacity greater than or equal to 65 kW, including packaged air-conditioners, split systems, and variable refrigerant flow units, must have a minimum energy efficiency ratio of 4.0 Wr/Winput power for cooling when tested in accordance with AS/NZS ISO 13256.1 at test condition C3, where input power includes both compressor and fan input power.

(2) Assessed individually or collectively, a building’s air-cooled unitary air-conditioning equipment, including packaged air-conditioners, split systems, and variable refrigerant flow units, must have a weighted efficiency index greater than 1—

calculated using the following formula, based on the energy efficiency ratio, [formula] , where—

[formula] = the weighted efficiency index of the unitary air-conditioners serving a building, assessed based on their rated Energy Efficiency Ratios; and

for each air-conditioner, [formula] —

[formula] = the tested energy efficiency ratio, determined in accordance with MEPS; and

[formula] = the rated cooling capacity determined in accordance with MEPS; and

[formula] = the applicable nominal minimum energy efficiency ratio in Table J6D12a; or

calculated using the following formula, based on the Total Cooling Seasonal Performance Factor, [formula] , where—

[formula] = the weighted efficiency index of the unitary air-conditioners serving a building, assessed based on their rated Total Cooling Seasonal Performance Factors; and

for each air-conditioner, [formula] —

[formula] = the mixed zone Total Cooling Seasonal Performance Factor, determined in accordance with MEPS for the commercial based use of the product; and

[formula] = the rated cooling capacity determined in accordance with MEPS; and

[formula] = the applicable nominal minimum energy efficiency ratio in Table J6D12b.

(3) Where the weighted efficiency index contribution of an air-conditioner is assessed using the formula at (2)(a), air-cooled unitary air-conditioners, including packaged air-conditioners, split systems and variable refrigerant flow units, must have—

variable speed outdoor fans; and

at least one—

digital scroll compressor; or

inverter driven compressor.

(4) The compressor required by 3(b) must be sized sufficiently to allow the unit to modulate across 50% to 100% of its rated cooling capacity.

(5) The requirements of (2) to (4) do not apply to—

unitary air-conditioners with a rated cooling capacity of less than 10 kW; or

unitary air-conditioners that serve only a Class 4 part of a building.

Table J6D12a Nominal minimum energy efficiency ratio figures for air-cooled unitary air-conditioning systems

Rated cooling capacity

Unitary systems other than variable refrigerant flow units

Variable refrigerant flow units

≤ 39 kW

3.3

3.8

> 39 kW

3.1

3.4

Table J6D12b Nominal minimum TCSPF figures for air-cooled unitary air-conditioning systems

Rated cooling capacity

Unitary systems other than variable refrigerant flow units

≤ 30 kW

3.6

> 30 kW

3.5

Tables

Changed since NCC 2022. See NCC 2022 Volume One J6D12, or show what changed.

Unitary air-conditioning equipment (1) Water-to-air unitary air-conditioners with a rated capacity greater than or equal to 65 kW, including packaged air-conditioners, split systems, and variable refrigerant flow systems units, must comply with MEPS and for a capacity greater than or equal to 65 kWr — where water cooled, have a minimum energy efficiency ratio of 4.0 Wr/Winputpower for cooling when tested in accordance with AS/NZS 3823.1.2 at test condition T1, where input power includes both compressor and fan input power; or where air cooled, have a minimum energy efficiency ratio of 2.9 Wr/Winput power for cooling when tested in accordance with AS/NZS 3823.1.2 ISO 13256.1 at test condition T1, C3, where input power includes both compressor and fan input power. (2) Assessed individually or collectively, a building’s air-cooled unitary air-conditioning equipment, including packaged air-conditioners, split systems, and variable refrigerant flow units, must have a weighted efficiency index greater than 1 — calculated using the following formula, based on the energy efficiency ratio, [formula] , where — [formula] = the weighted efficiency index of the unitary air-conditioners serving a building, assessed based on their rated Energy Efficiency Ratios; and for each air-conditioner, [formula] — [formula] = the tested energy efficiency ratio, determined in accordance with MEPS; and [formula] = the rated cooling capacity determined in accordance with MEPS; and [formula] = the applicable nominal minimum energy efficiency ratio in Table J6D12a; or calculated using the following formula, based on the Total Cooling Seasonal Performance Factor, [formula] , where — [formula] = the weighted efficiency index of the unitary air-conditioners serving a building, assessed based on their rated Total Cooling Seasonal Performance Factors; and for each air-conditioner, [formula] — [formula] = the mixed zone Total Cooling Seasonal Performance Factor, determined in accordance with MEPS for the commercial based use of the product; and [formula] = the rated cooling capacity determined in accordance with MEPS; and [formula] = the applicable nominal minimum energy efficiency ratio in Table J6D12b. (3) Where the weighted efficiency index contribution of an air-conditioner is assessed using the formula at (2)(a), air-cooled unitary air-conditioners, including packaged air-conditioners, split systems and variable refrigerant flow units, must have — variable speed outdoor fans; and at least one — digital scroll compressor; or inverter driven compressor. (4) The compressor required by 3(b) must be sized sufficiently to allow the unit to modulate across 50% to 100% of its rated cooling capacity. (5) The requirements of (2) to (4) do not apply to — unitary air-conditioners with a rated cooling capacity of less than 10 kW; or unitary air-conditioners that serve only a Class 4 part of a building. Table J6D12a Nominal minimum energy efficiency ratio figures for air-cooled unitary air-conditioning systems Rated cooling capacity Unitary systems other than variable refrigerant flow units Variable refrigerant flow units ≤ 39 kW 3.3 3.8 > 39 kW 3.1 3.4 Table J6D12b Nominal minimum TCSPF figures for air-cooled unitary air-conditioning systems Rated cooling capacity Unitary systems other than variable refrigerant flow units ≤ 30 kW 3.6 > 30 kW 3.5

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J6D12? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →

Defined terms used