Table · NCC 2025 Volume One

Table J6D4 Required outdoor air treatment

Part J6 Air-conditioning and ventilation

Open Table J6D4 on NCC Online ↗
Climate zoneOutdoor air flow (L/s)Required measure - where demand control ventilation is appropriateRequired measure - where demand control ventilation is not appropriate
1≤120No required measureNo required measure
1>120 to ≤2000Modulating controlNo required measure
1>2000Modulating controlIndirect evaporative cooling system
2≤400No required measureNo required measure
2>400Modulating controlNo required measure
3≤400No required measureNo required measure
3>400 to ≤2000Modulating controlNo required measure
3>2000Modulating controlIndirect evaporative cooling system
4≤400No required measureNo required measure
4>400 to ≤500Modulating controlNo required measure
4>500Modulating controlEnergy reclaiming system
5≤400No required measureNo required measure
5>400 to ≤1000Modulating controlNo required measure
5>1000Modulating controlEnergy reclaiming system
6≤500No required measureNo required measure
6>500Modulating controlEnergy reclaiming system
7≤250No required measureNo required measure
7>250Modulating controlEnergy reclaiming system
8≤100No required measureNo required measure
8>100 to ≤250Modulating controlNo required measure
8>250Modulating controlEnergy reclaiming system

Table for J6D4 Mechanical ventilation system control

Changed since NCC 2022. See NCC 2022 Volume One Table J6D4, or show what changed.

Climate zone | Outdoor air flow (L/s) | Required measure - where demand control ventilation is appropriate | Required measure - where demand control ventilation is not appropriate 1 | >500 ≤120 | No required measure | No required measure 1 | >120 to ≤2000 | Modulating control | No required measure 1 | >2000 | Modulating control | Indirect evaporative cooling system 2 | Not applicable ≤400 | No required measure | No required measure 2 | >400 | Modulating control | No required measure 3 | ≤400 | No required measure | No required measure 3 | >400 to ≤2000 | Modulating control | No required measure 3 | >2000 | Modulating control | Indirect evaporative cooling system 4 | ≤400 | No required measure | No required measure 4 | >400 to ≤500 | Modulating control | No required measure 4 | >500 | Modulating control | Energy reclaiming system 5 | ≤400 | No required measure | No required measure 5 | >400 to ≤1000 | Modulating control | No required measure 5 | >1000 | Modulating control 4 and | Energy reclaiming system 6 | ≤500 | No required measure | No required measure 6 | >500 | Modulating control or energy | Energy reclaiming system 5 7 | >1000 ≤250 | No required measure | No required measure 7 | >250 | Modulating control or energy | Energy reclaiming system 7 and 8 | ≤100 | No required measure | No required measure 8 | >100 to ≤250 | Modulating control | No required measure 8 | >250 | Modulating control or energy | Energy reclaiming system

Removed words are struck through; added words are highlighted. Comparison of the text only.