Table J6D4 Required outdoor air treatment
Part J6 Air-conditioning and ventilation
| Climate zone | Outdoor air flow (L/s) | Required measure - where demand control ventilation is appropriate | Required measure - where demand control ventilation is not appropriate |
|---|---|---|---|
| 1 | ≤120 | No required measure | No required measure |
| 1 | >120 to ≤2000 | Modulating control | No required measure |
| 1 | >2000 | Modulating control | Indirect evaporative cooling system |
| 2 | ≤400 | No required measure | No required measure |
| 2 | >400 | Modulating control | No required measure |
| 3 | ≤400 | No required measure | No required measure |
| 3 | >400 to ≤2000 | Modulating control | No required measure |
| 3 | >2000 | Modulating control | Indirect evaporative cooling system |
| 4 | ≤400 | No required measure | No required measure |
| 4 | >400 to ≤500 | Modulating control | No required measure |
| 4 | >500 | Modulating control | Energy reclaiming system |
| 5 | ≤400 | No required measure | No required measure |
| 5 | >400 to ≤1000 | Modulating control | No required measure |
| 5 | >1000 | Modulating control | Energy reclaiming system |
| 6 | ≤500 | No required measure | No required measure |
| 6 | >500 | Modulating control | Energy reclaiming system |
| 7 | ≤250 | No required measure | No required measure |
| 7 | >250 | Modulating control | Energy reclaiming system |
| 8 | ≤100 | No required measure | No required measure |
| 8 | >100 to ≤250 | Modulating control | No required measure |
| 8 | >250 | Modulating control | Energy reclaiming system |
Table for J6D4 Mechanical ventilation system control
Changed since NCC 2022. See NCC 2022 Volume One Table J6D4, or show what changed.
Climate zone | Outdoor air flow (L/s) | Required measure - where demand control ventilation is appropriate | Required measure - where demand control ventilation is not appropriate 1 | >500 ≤120 | No required measure | No required measure 1 | >120 to ≤2000 | Modulating control | No required measure 1 | >2000 | Modulating control | Indirect evaporative cooling system 2 | Not applicable ≤400 | No required measure | No required measure 2 | >400 | Modulating control | No required measure 3 | ≤400 | No required measure | No required measure 3 | >400 to ≤2000 | Modulating control | No required measure 3 | >2000 | Modulating control | Indirect evaporative cooling system 4 | ≤400 | No required measure | No required measure 4 | >400 to ≤500 | Modulating control | No required measure 4 | >500 | Modulating control | Energy reclaiming system 5 | ≤400 | No required measure | No required measure 5 | >400 to ≤1000 | Modulating control | No required measure 5 | >1000 | Modulating control 4 and | Energy reclaiming system 6 | ≤500 | No required measure | No required measure 6 | >500 | Modulating control or energy | Energy reclaiming system 5 7 | >1000 ≤250 | No required measure | No required measure 7 | >250 | Modulating control or energy | Energy reclaiming system 7 and 8 | ≤100 | No required measure | No required measure 8 | >100 to ≤250 | Modulating control | No required measure 8 | >250 | Modulating control or energy | Energy reclaiming system
Removed words are struck through; added words are highlighted. Comparison of the text only.