Table J6D5a Minimum fan performance grade
Part J6 Air-conditioning and ventilation
| Fan type | Installation type A or C | Installation type B or D |
|---|---|---|
| All fans as a component of an air-handling unit or fan coil unit | 61 | 64 |
| Axial | 40 | 58 |
| Mixed flow | 50 | 62 |
| Centrifugal forward-curved | 44 | 49 |
| Centrifugal radial bladed | 44 | 49 |
| Centrifugal backward-curved | 61 | 64 |
Table Notes
Installation type A means an arrangement where the fan is installed with free inlet and outlet conditions.
Installation type B means an arrangement where the fan is installed with a free inlet and a duct at its outlet.
Installation type C means an arrangement where the fan is installed with a duct fitted to its inlet and with free outlet conditions.
Installation type D means an arrangement where the fan is installed with a duct fitted to its inlet and outlet.
Table for J6D5 Fans and duct systems
Changed since NCC 2022. See NCC 2022 Volume One Table J6D5a, or show what changed.
Fan type | Installation type A or C | Installation type B or D Axial — All fans as a component of an air handling air-handling unit or fan coil unit | 46.0 61 | 51.5 64 Axial — other | 42.0 40 | 61.0 58 Mixed flow — as a component of an air handling unit or fan coil unit | 46.0 50 | 51.5 Mixed flow — other 62 Centrifugal forward-curved | 52.5 44 | 65.0 Centrifugal forward — curved | 46.0 | 51.5 49 Centrifugal radial bladed | 46.0 44 | 51.5 49 Centrifugal backward-curved | 64.0 61 | 64.0 64 Table Notes Installation type A means an arrangement where the … installed with a duct fitted to its inlet and outlet.
Removed words are struck through; added words are highlighted. Comparison of the text only.