Table · NCC 2025 Volume One
Table J6D5d Maximum coil pressure drop
Part J6 Air-conditioning and ventilation
| Number of rows | Maximum pressure drop (Pa) |
|---|---|
| 1 | 30 |
| 2 | 50 |
| 4 | 90 |
| 6 | 130 |
| 8 | 175 |
| 10 | 220 |
Table for J6D5 Fans and duct systems
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J6D5d.