Table · NCC 2022 Volume One

Table J6D5d Maximum coil pressure drop

Part J6 Air-conditioning and ventilation

Open Table J6D5d on NCC Online ↗
Number of rowsMaximum pressure drop (Pa)
130
250
490
6130
8175
10220

Table for J6D5 Fans and duct systems

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D5d.