Table S35C2b Occupancy and operation profiles of a Class 3 hotel

Specification 35 Modelling profiles for J1V3

Open Table S35C2b on NCC Online ↗
Time period (local standard time)Occupancy (Daily)Artificial lighting (Daily)Appliances and equipment (Daily)Air-conditioning (Daily)
12:00am to 1:00am90%5%20%On
1:00am to 2:00am90%5%20%On
2:00am to 3:00am90%5%15%On
3:00am to 4:00am90%5%15%On
4:00am to 5:00am90%5%15%On
5:00am to 6:00am80%25%15%On
6:00am to 7:00am70%80%40%On
7:00am to 8:00am60%80%80%On
8:00am to 9:00am60%50%50%On
9:00am to 10:00am30%20%30%On
10:00am to 11:00am10%20%20%Off
11:00am to 12:00pm10%20%20%Off
12:00pm to 1:00pm10%20%20%Off
1:00pm to 2:00pm10%20%20%Off
2:00pm to 3:00pm10%20%20%Off
3:00pm to 4:00pm10%20%20%Off
4:00pm to 5:00pm20%20%20%On
5:00pm to 6:00pm30%50%40%On
6:00pm to 7:00pm40%50%40%On
7:00pm to 8:00pm50%50%50%On
8:00pm to 9:00pm60%50%60%On
9:00pm to 10:00pm70%50%60%On
10:00pm to 11:00pm70%50%40%On
11:00pm to 12:00am90%50%20%On

Table Notes

The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the Class 3 building.

The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.

The air-conditioning profile is expressed as the plant status.