NCC 2025 Volume One
Specification 35 Modelling profiles for J1V3
16 clauses · Open on NCC Online ↗
- S35C1 ScopeThis Specification contains modelling profiles as referenced in S34C3(6)(g).
- Table * * * * * This table reference has been deliberately left blank
- Table S35C2b Occupancy and operation profiles of a Class 3 hotelTime period (local standard time) | Occupancy (Daily) | Artificial lighting (Daily) | Appliances and equipment (Daily) | Air-conditioning (Daily)…
- Table S35C2c Weekday occupancy and operation profiles of a Class 5 building, a Class 7 warehouse, a Class 8 Laboratory or a Class 9a clinic, day surgery or procedure unitTime period (local standard time) | Occupancy (Monday to Friday) | Artificial lighting (Monday to Friday) | Appliances and equipment (Monday to…
- Table S35C2d Weekend occupancy and operation profiles of a Class 5 building, a Class 7 warehouse, a Class 8 Laboratory or a Class 9a clinic, day surgery or procedure unitTime period (local standard time) | Occupancy (Saturday, Sunday and holidays) | Artificial lighting (Saturday, Sunday and holidays) | Appliances and…
- Table S35C2e Occupancy and operation profiles of a Class 6 shop or shopping centreTime period (local standard time) | Occupancy (Daily) | Artificial lighting (Daily) | Appliances and equipment (Daily) | Air-conditioning (Daily)…
- Table S35C2f Occupancy and operation profiles of a Class 6 restaurant or cafeTime period (local standard time) | Occupancy (Monday to Saturday) | Artificial lighting (Monday to Saturday) | Appliances and equipment (Monday to…
- Table S35C2g Occupancy and operation profiles of a Class 9a ward areaTime period (local standard time) | Occupancy (Daily) | Artificial lighting (Daily) | Air-conditioning (Daily) 12:00am to 1:00am | 70% | 5% | On…
- Table S35C2h Occupancy and operation profiles of a Class 9b theatre or cinemaTime period (local standard time) | Occupancy (Monday to Friday) | Occupancy (Saturday and Sunday) | Artificial lighting (Monday to Friday) |…
- Table S35C2i Occupancy and operation profiles of a Class 9b conference facilityHour | Occupancy (Daily) | Artificial lighting and equipment (Daily) | Air-conditioning (Daily) 12:00am to 1:00am | 0% | 15% | Off 1:00am to 2:00am…
- Table S35C2j Occupancy and operation profiles of a Class 9b schoolTime period (local standard time) | Occupancy (Monday to Friday) | Artificial lighting (Monday to Friday) | Appliances and equipment (Monday to…
- Table S35C2k Occupancy and operation profiles of a Class 9c aged care facilityTime period (local standard time) | Occupancy (Monday to Friday) | Occupancy (Saturday, Sunday and holidays) | Artificial lighting (Daily) |…
- Table S35C2l Internal heat gains for appliances and equipmentApplication | Internal sensible heat gain rate Class 9a building ward area | 5 W/m2 averaged for 24 hours per day, 7 days per week, continuous…
- Table S35C2m Heated water supply consumption ratesApplication | Daily consumption rate at 60°C Residential part of a hotel or motel | 100 L/sole-occupancy unit Dormitory, boarding house, guest…
- Table S35C2n Internal heat gains for occupants and hot mealsApplication | Internal heat gains per person Dining room, restaurant or cafe | 80 W sensible heat gain and 80 W latent heat gain The average…
- S35C2 Modelling profilesThe air-conditioning, must be modelled on the basis of— the daily occupancy and operation profiles in Tables S35C2b, S35C2c, S35C2d, S35C2e, S35C2f,…